Other Control
• In order to set the SLAVE 2 to operation prohibition
mode, set No. 40 of Setting mode 2 to "SLAVE 2
OPERATION PROHIBITION".
∗
• In the case of multi-outdoor-unit system, "Inhibition of operation" is not set with each
compressor individually.
• In the case of multi-outdoor-unit system, when the above "Inhibition of operation" is set,
outdoor unit rotation is not functional.
Note :
Reset the power supply during the outdoor unit is stopping to cancel the
automatic backup operation forcibly.
5.3
Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using "Demand 1 Setting" or "Demand 2 Setting".
To operate the unit with this mode, additional setting of "Continuous Demand Setting" or
external input by external control adapter is required.
Demand 1
Demand 2
5.4
Heating Operation Prohibition
Heating operation is prohibited above 24°C ambient temperature.
102
(Procedure)
(1) Press and hold the PAGE button (BS1) for a period
of 5 seconds or more.
(2) Press the OPERATION button (BS2) 40 times.
(3) Press the CHECK button (BS3) once.
(4) Press the OPERATION button (BS2) once.
(5) Press the CHECK button (BS3) twice.
(6) Press the PAGE button (BS1) once.
Set item
Condition
Mode 1
Mode 2
Mode 3
LED display (7:ON
H1P---H7P
7777777
777777
777 7 7777
777777
777779 9
77777
77779 9 7 7
7777777
777777
7777777
77
7777
Content
The compressor operates at approx. 60% or less of rating.
The compressor operates at approx. 70% or less of rating.
The compressor operates at approx. 80% or less of rating.
The compressor operates at approx. 40% or less of rating.
Si39-407
:OFF
:Blink)
7 7
9 9
777
(Factory set)
Function