Daikin RXYQ5-48MAY1 Service Manual page 214

R410a heat pump 50hz
Table of Contents

Advertisement

Si39-407
Troubleshooting
Note:
Refer check 8, 9 and 12 to P.264
Troubleshooting
1A
Check No. 12
Check on pulse input of
position signal of fan inverter
PCB
Is the LED
(HAP) on fan inverter
PCB blinking?
YES
Check No. 8
Check on connector of fan
motor (Power supply cable)
Are the
resistance values
between phases of
U, V, W balanced?
Is there any short
circuiting between
phases of
U, V, W?
YES
Check No. 9
Check on connector of fan
motor (Signal wire)
Is the
resistance value
between Vcc and UVW,
and GND and UVW
balanced?
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
NO
~
265.
Replace the fan inverter
PCB.
Replace the fan motor of
outdoor unit.
Replace the fan motor of
outdoor unit.
Replace the fan inverter
PCB.
(V3077)
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents