Daikin RXYQ5-48MAY1 Service Manual page 139

R410a heat pump 50hz
Table of Contents

Advertisement

Field Setting
Air Flow Adjustment - Ceiling height
Make the following setting according to the ceiling height. The setting position No. is set to "01"
at the factory.
13 (23)
13 (23)
13 (23)
Air Flow Direction Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to "01."
Setting Table
Setting of Air Flow Direction Adjustment
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Down-flow operation: Yes
Down-flow operation: No
128
In the Case of FXAQ, FXHQ
Setting Switch
Mode No.
No.
13(23)
0
In the Case of FXFQ25~80
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
In the Case of FXFQ100~125
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
In the Case of FXUQ71~125
First
Second
Mode
code
code
No.
No.
No.
01
Standard (N)
0
02
High Ceiling (H)
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.8 m
Mode No.
First Code No.
13 (23)
1
Setting
Setting Position
No.
01
Wall-mounted type: Standard
02
Wall-mounted type: Slight increase
03
Wall-mounted type: Normal increase
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
Setting
4-way Outlets
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
Setting
4-way Outlets
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
Lower than 3.0 m Lower than 3.5 m Lower than 3.8 m
Second Code
No.
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Mode No.
First Code No.
13 (23)
Setting
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Ceiling height
3-way Outlets
2-way Outlets
Setting
Second Code No.
3
01
02
Test Operation
Si39-407