MENU FAN (FAN)
Parameter
Default Limits
F02
1
0 - 1
F03
50
40 - F04
F04
100
F03 - 100
F05
30
0 - 50
F06
6
0 - 10
F07
15
10 - 60
DEFROST BRANCH (DFR)
Parameter
Default Limits
d01
0
0 - 1 - 2
d02
1
0 - 1
d03
-3
-40 - d04
d04
13
d03 - 40
d05
10
10 - 150
d07
5
2 - 150
d08
45
15 - 120
d09
0
0 -1
d13
60
30 - 180
Unit
Description
Num(1)
Sets the operating logic (0= ON/OFF) (1= modulating)
Num(1)
Minimum fan speed. % of maximum voltage. From 40 to 100%
Num(1)
Maximum fan speed. % of maximum voltage. From F03 to 100%
°C
Temperature above which the fan must run at minimum speed
°C
Temperature differential on max speed of the fan
Water temperature above which the fan modulates between the
°C
values F04 and F03
Unit
Description
Defrost activation [0 = disabled; 1= active with hot gas; 2 not
Num(1)
available]
Num(1)
Defrost exit mode [0 = per time; 1 = per temperature]
°C
Evaporation temperature under which a defrost cycle starts
°C
Evaporation temperature over which a defrost cycle ends
Minimum permanence time of probe S03 at defrost starting
sec
value
min
Defrost cycle duration if d02=0, or max. cycle duration if d02=1
min
Minimum delay between two consecutive defrosts
Num(1)
Fan status during defrost [0 = OFF; 1 = ON]
sec
Equalization time upon starting
17