Precautions For Device Replacement; Precautions When Replacing The Parameters - Mitsubishi MELSEC FX3U Series Handbook

Hide thumbs Also See for MELSEC FX3U Series:
Table of Contents

Advertisement

Precautions for Device Replacement

Precautions for Device Replacement
Index modification of the S device (state) cannot be made on the MELSEC iQ-F. Replace as follows.
• When the S device without state management has its index modified, replace to M device to use.
• When the S device used for state management has its index modified and used for the ZRST instructions, program the
ZRST instructions for each batch-clear pattern.
For GX Works3 whose version is earlier than 1.030G, the assigned device of the global label cannot be read out.
• Information of the assigned device in GX Works2 is input in the comment field. Refer to the comment field to assign the
device again.
• When special M and special D have been assigned, they will be replaced and assigned to SM and SD.
If S device is set to the device memory data or device initial data created using GX Works2, it will be deleted.
If there is a device that is not supported by the MELSEC iQ-F Series in the program created using GX Works2, the device will
be changed to SM4095/SD4095.
The default value is set to the parameter setting of device points.
SM/SD Device Replacement
Devices, M8000 and later and D8000 and later of FX3U/FX3UC, will be changed to devices, SM8000 and later and SD8000
and later. However, some devices may be changed depending on the version of GX Works3. For details, refer to the following.
FX3U/
After replacing to MELSEC iQ-F
FX3UC
GX Works3 version
1.032J and earlier
M8004
SM8004
M8009
SM8009
M8061
SM8061
M8064
SM8064
M8065
SM8065
M8066
SM8066
M8091
SM8091
M8131
SM8131
M8133
SM8133
M8138
SM8138
M8139
SM8139
M8165
SM8165
M8235
SM8235
M8236
SM8236
M8237
SM8237
M8238
SM8238
M8239
SM8239
4.3

Precautions when Replacing the Parameters

When converting projects of the FX3 Series to MELSEC iQ-F projects, the setting data of the parameters (PLC parameter and
network parameter) and special module (intelligent function module) will be deleted. Therefore, it is necessary to reset the
data with GX Works3.
Also, GX Works3 does not support the following parameters of FX3 Series, so it is necessary to set with GX Works3 again.
• Network parameter (CC-Link)
• Intelligent function module parameter (AnyWireASLINK)
4 Conversion of the Projects
48
4.3 Precautions when Replacing the Parameters
GX Works3 version
1.035M and later
SM0
SM0
SM0
SM0
SM0
SM0
SM701
SM5001
SM5001
SM5001
SM5000
SM703
SM4580
SM4581
SM4582
SM4583
SM4584
FX3U/
After replacing to MELSEC iQ-F
FX3UC
GX Works3 version
1.032J and earlier
M8240
SM8240
M8241
SM8241
M8242
SM8242
M8243
SM8243
M8244
SM8244
M8245
SM8245
M8318
SM8318
M8489
SM8489
D8004
SD8004
D8009
SD8009
D8061
SD8061
D8064
SD8064
D8065
SD8065
D8066
SD8066
D8101
SD8101
D8166
SD8166
D8489
SD8489
GX Works3 version
1.035M and later
SM4585
SM4580
SM4582
SM4584
SM4580
SM4582
SM0
SM0
SD0
SD0
SD0
SD0
SD0
SD0
SD8001
SD83
SD0

Advertisement