Emerson Oxymitter 5000 Instruction Manual page 151

Oxygen transmitter with foundation fieldbus communications
Hide thumbs Also See for Oxymitter 5000:
Table of Contents

Advertisement

Alarm Detection
Model 4081FG Oxygen Analyzer with F
Initialization Manual (IMan)—The output path is not complete (for
example, the cascade-to-slave path might not be open). In IMan mode,
OUT tracks BKCAL_IN.
Out of Service (O/S)—The block is not processed. The OUT status is
set to Bad: Out of Service . The BLOCK_ERR parameter shows
Out of service.
You can configure the Man, Auto, Cas, and O/S modes as permitted
modes for operator entry.
A block alarm will be generated whenever the BLOCK_ERR has an
error bit set. The types of block error for the AI block are defined above.
Process alarm detection is based on the PV value. You can configure the
alarm limits of the following standard alarms:
• High (HI_LIM)
• High high (HI_HI_LIM)
• Low (LO_LIM)
• Low low (LO_LO_LIM)
Additional process alarm detection is based on the difference between
SP and PV values and can be configured via the following parameters:
• Deviation high (DV_HI_LIM)
• Deviation low (DV_LO_LIM)
In order to avoid alarm chattering when the variable is oscillating
around the alarm limit, an alarm hysteresis in percent of the PV span
can be set using the ALARM_HYS parameter. The priority of each
alarm is set in the following parameters:
• HI_PRI
• HI_HI_PRI
• LO_PRI
• LO_LO_PRI
• DV_HI_PRI
• DV_LO_PRI
Alarms are grouped into five levels of priority:
Priority
Priority Description
Number
0
The priority of an alarm condition changes to ) after the condition that caused
the alarm is corrected.
1
An alarm condition with a priority of 1 is recognized by the system, but is not
reported to the operator.
2
An alarm condition with a priority of 2 is reported to the operator, but does not
require operator attention (such as diagnostics and system alerts).
3-7
Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
8-15
Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
fieldbus Communications
OUNDATION
C
C-9