FIGURE B-6. Situation #2 Diagram.
TABLE B-5. Analog Input Function
Block Configuration for a Pressure
Transmitter used in Level Measurement
(Situation #2).
Model 4081FG Oxygen Analyzer with F
Situation #2
The transmitter in situation #1 is installed below the tank in a position
where the liquid column in the impulse line, when the tank is empty, is
equivalent to 2.0 psi (see Figure B-6).
16 ft
0 ft
Solution
Table B-5 lists the appropriate configuration settings.
Parameter
L_TYPE
XD_SCALE
OUT_SCALE
fieldbus Communications
OUNDATION
Empty Tank
2.0 psi measured at
the transmitter
Configured Values
Indirect
2 to 9 psi
0 to 16 ft
B
B-11