Emerson Oxymitter 5000 Instruction Manual page 146

Oxygen transmitter with foundation fieldbus communications
Hide thumbs Also See for Oxymitter 5000:
Table of Contents

Advertisement

Model 4081FG Oxygen Analyzer with F
Parameter
Index
Number
OUT-LO_LIM
29
OUT_SCALE
11
PV
07
PV_FTIME
16
PV_SCALE
10
RATE
26
RCAS_IN
32
RCAS_OUT
35
RESET
24
ROUT_IN
33
ROUT_OUT
36
SHED_OPT
34
SP
08
SP_FTIME
69
SP_HI_LIM
21
SP_LO_LIM
22
SP_RATE_DN
19
SP-RATE_UP
20
SP_WORK
68
STATUS_OPTS
14
STRATEGY
03
ST_REV
01
STRUCTURE.
75
CONFIG
TAG_DESC
02
TRK_IN_D
38
C-4
OUNDATION
Units
EU of OUT_SCALE
The minimum output value allowed
None
The high and low scale values, engineering units code, and number of digits to the right of
the decimal point associated with OUT.
EU of PV_SCALE
The process variable used in block execution.
Seconds
The time constant of the first-order PV filter. It is the time required for a 63 percent change
in the IN value.
None
The high and low scale values, engineering units code, and number of digits to the right of
the decimal point associated with PV.
Seconds
The derivative action time constant.
EU of PV_SCALE
Target setpoint and status that is provided by a supervisory host. Used when mode is RCAS.
EU of PV_SCALE
Block setpoint and status after ramping, filtering, and limiting that is provided to a supervisory
host for back calculation to allow action to be taken under limiting conditions or mode
change. Used when mode is RCAS.
Seconds per repeat
The integral action time constant.
EU of OUT_SCALE
Target output and status that is provided by a supervisory host. Used when mode is ROUT.
EU of OUT_SCALE
Block output that is provided to a supervisory host for a back calculation to allow action to
be taken under limiting conditions or mode change. Used when mode is RCAS.
None
Defines action to be taken on remote control device timeout.
EU of PV_SCALE
The target block setpoint value. It is the result of setpoint limiting and setpoint
rate of change limiting.
Seconds
The time constant of the first-order SP filter. It is the time required for a 63 percent change
in the IN value.
EU of PV_SCALE
The highest SP value allowed.
EU of PV_SCALE
The lowest SP value allowed.
EU of PV_SCALE per
Ramp rate for downward SP changes. When the ramp rate is set to zero, the SP
second
is used immediately.
EU of PV_SCALE per
Ramp rate for upward SP changes. When the ramp rate is set to zero,
second
the SP is used immediately.
EU of PV_SCALE
The working setpoint of the block after limiting and filtering is applied.
None
Allows you to select options for status handling and processing. The supported status option
for the PID block is Target to Manual if Bad IN.
None
The strategy field can be used to identify grouping of blocks. This data is not checked or
processed by the block.
None
The revision level of the static data associated with the function block. The revision value will
be incremented each time a static parameter value in the block is changed.
None
Defines PID equation structure to apply controller action.
None
The user description of the intended application of the block.
None
Discrete input that initiates external tracking.
fieldbus Communications