List Of Number Of Remote Points And Remote Nos - Mitsubishi FX2N-32CCL User Manual

Cc-link interface block
Table of Contents

Advertisement

FX
-32CCL CC-Link Interface Block
2N
4.2

List of number of remote points and remote Nos.

In the FX
-32CCL, the number of remote points vary depending on the selected number of stations (1 to 4).
2N
Thirty-two remote input points and 32 remote output points are available in one station. However, the
upper 16 points of the final station are occupied by the CC-Link as the system area.
Four read points and four write points are available as remote registers in one station.
Table of number of remote points and remote Nos. in accordance with selected number of stations
Number
of
Type
stations
User area
1
System area
User area
2
System area
User area
3
System area
User area
4
System area
Remote input
Remote output
RX00 to RX0F
RY00 to RY0F
(16 points)
(16 points)
RX10 to RX1F
RY10 to RY1F
(16 points)
(16 points)
RX00 to RX2F
RY00 to RY2F
(48 points)
(48 points)
RX30 to RX3F
RY30 to RY3F
(16 points)
(16 points)
RX00 to RX4F
RY00 to RY4F
(80 points)
(80 points)
RX50 to RX5F
RY50 to RY5F
(16 points)
(16 points)
RX00 to RX6F
RY00 to RY6F
(112 points)
(112 points)
RX70 to RX7F
RY70 to RY7F
(16 points)
(16 points)
Setting of Remote Device Stations 4
Remote register for
Remote register for
write
RWr0 to RWr3
(4 points)
RWr0 to RWr7
(8 points)
RWr0 to RWrB
(12 points)
RWr0 to RWrF
(16 points)
read
RWw0 to RWw3
(4 points)
RWw0 to RWw7
(8 points)
RWw0 to RWwB
(12 points)
RWw0 to RWwF
(16 points)
4-3