Mitsubishi FX2N-32CCL User Manual page 42

Cc-link interface block
Table of Contents

Advertisement

FX
-32CCL CC-Link Interface Block
2N
Preparation
1 ) Set the station No. set switch, the mode set switch, the transmission set switch and the condition set
switch provided on the master unit. (
2 ) Set the station No. set switch, the number of occupied stations set switch and the transmission speed set
switch provided on the FX
Item
Station No.
Number of
occupied
stations
Transmission
speed
Assignment of
number of
remote points
and No.
Number of
points and No.
are deter-
mined by
selected num-
ber of occu-
pied stations.
-32CCL. (
2N
Setting of FX
-32CCL (station No. 1)
2N
1 (rotary switch)
4 (rotary switch)
In accordance with setting in master unit (rotary switch)
Number of remote points and No. when four
stations are occupied
•Remote input:
RX00 to RX6F (112 points) for user area
RX70 to RX7F (16 points) for system area
•Remote output:
RY00 to RY6F (112 points) for user area
RY70 to RY7F (16 points) for system area
•Remote register:
RWr0 to RWrF (16 points) for write
RWw0 to RWwF(16 points) for read
User's manual of master unit)
4.1)
Setting of FX
5 (rotary switch)
2 (rotary switch)
Number of remote points and No. when two
stations are occupied
•Remote input:
RX00 to RX2F (48 points) for user area
RX30 to RX3F (16 points) for system area
•Remote output:
RY00 to RY2F (48 points) for user area
RY30 to RY3F (16 points) for system area
•Remote register:
RWr0 to RWr7 (8 points) for write
RWw0 to RWw7 (8 points) for read
Programming Examples 6
-32CCL (station No. 5)
2N
6-2