Mitsubishi FX2N-32CCL User Manual page 22

Cc-link interface block
Table of Contents

Advertisement

FX
-32CCL CC-Link Interface Block
2N
Wiring of twisted pair cable
Wire the FX
-32CCL and the CC-Link using shielded twisted pair cables as shown in the figure below.
2N
T erm inal
resistor
C lass 3
grounding
Connect the terminals DA and DA, DB and DB as well as DG and DG of each station with shielded
twisted
pair cables. Because two DA terminals and two DB terminals are provided in the FX
a next station can be easily connected.
Connect the SLD terminal of each station to a shield of a shielded twisted pair cable.
Perform Class 3 grounding to the FG terminal of each station.
Wiring of each station can be performed from any point without regard to the station No.
When the FX
DA and DB of the FX
The maximum transmission distance and the distance between stations in the CC-Link system vary
depending on the selected transmission speed. For the details, refer to the maximum transmission dis-
tance described in "2.2 General specifications and performance specifications" or the specifications
described in the manual of the CC-Link master unit.
M aster
F X
unit
D A
D B
D G
S hielded twisted
S LD
pair cable
F G
C lass 3
grounding
-32CCL is used as the terminal station, connect a terminal resistor between the terminals
2N
-32CCL. The terminal resistor is packed together with the Master unit.
2N
R em ote I/O
-32C C L
2N
D A
D A
D B
D B
D G
S LD
F G
C lass 3
grounding
Connection and Wiring 3
unit
D A
T erm inal
resistor
D B
D G
S LD
F G
2N
3-4
-32CCL,