[BFM #24 (set value of baud rate)]
The setting of the baud rate (transmission speed) set switch provided in the FX
numeric of 0 to 4.
The saved value is determined when the power of the FX PC is turned on. If the setting is changed while the
power is turned on, the changed setting becomes valid when the power is turned on at the next time.
0: 156 kbps
1: 625 kbps
[BFM #25 (communication status)]
The communication status between the CC-Link and the information on the master PC are saved as the ON/
OFF information to b15 to b0.
The information on the master PC is valid exclusively while link communication is performed.
b0
CRC error
b1
Timeout error
b2 to b6
Reserved
b7
Linking is being executed.
[BFM #26 (CC-Link model code)]
The model code is saved in the following format.
Recognition code in
CC-Link system
[Set value of BFM #27 (its own station No.)]
The setting of the station No. set switch provided in the FX
The saved value is determined when the power of the FX PC is turned on. If the setting is changed while the
power is turned on, the changed setting becomes valid when the power is turned on at the next time.
2: 2.5 Mbps
3: 5 Mbps
01
01
H
Assignment of Buffer Memory (BFM) 5
4: 10 Mbps
b8
Master PC is running.
b9
Master PC error
b10 to b15 Reserved
Version No. of system software in the
FX
-32CCL
2N
-32CCL is saved as a numeric of 1 to 64.