VISTA-128BPT/128BPT-SIA/250BPT PROGRAMMING GUIDE
FIELD TITLE and DATA ENTRIES
∗06
QUICK EXIT (partition-specific)
0 = disable
1 = enable
If enabled, allows users to exit the armed partition without disarming and then rearming the partition.
Quick Exit is initiated by entering [#] + [9]. This restarts the exit delay. All rules of exit apply, including exit error logic.
UL
MUST BE SET TO 0 FOR UL INSTALLATIONS.
∗09
ENTRY DELAY #1 (partition-specific)
Enter 02-15 multiplied by 15 seconds.
00 = no delay.
Entry delay defines the delay time that allows users to re-enter the premises through a door that has been programmed as
an entry delay door and disarm the system without sounding an alarm. The system must be disarmed within this period or
an alarm will occur.
UL
THE DELAY MAY NOT EXCEED 45 SECONDS FOR UL INSTALLATIONS.
∗10
EXIT DELAY #1 (partition-specific)
Enter 02-15 multiplied by 15 seconds.
00 = no delay.
Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned to Entry Delay #1.
UL
THE DELAY MAY NOT EXCEED 45 SECONDS FOR UL INSTALLATIONS.
∗11
ENTRY DELAY #2 (partition-specific)
Enter 02-15 multiplied by 15 seconds.
00 = no delay.
Exit delay defines the delay period that allows users to leave the premises through a door that has been programmed as an
entry/exit delay door after arming the system without setting off the alarm.
UL
THE DELAY MAY NOT EXCEED 45 SECONDS FOR UL INSTALLATIONS.
∗12
EXIT DELAY #2 (partition-specific)
Enter 02-15 multiplied by 15 seconds.
00 = no delay.
Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned to Exit Delay #1.
UL
THE DELAY MAY NOT EXCEED 45 SECONDS FOR UL INSTALLATIONS.
∗13
ALARM SOUNDER DURATION (BELL TIMEOUT)
(partition-specific)
Enter 01-15 multiplied by 2 minutes.
Defines the length of time the Bell Output and the keypad's sounder will sound for all audible alarms.
UL
MUST BE MINIMUM 16 MINUTES FOR UL COMMERCIAL BURGLARY INSTALLATIONS.
∗14
RS232 INPUT
0 = Disable
1 = Enable
When enabled, sets RS232 input at TB4.
UL
AUTOMATION INPUT USING TB4 IS NOT PERMITTED IN UL INSTALLATIONS
∗15
KEYSWITCH ASSIGNMENT
Enter 1-8 partition keyswitch is being used.
Enter 0 if the keyswitch is not used.
• The keyswitch requires the use of zone 7 wired loop (zone 7 is no longer available as protection zone).
• The fire and panic alarm voltage triggers (J7) automatically become ARMING and READY status outputs for the
Keyswitch LEDs.
Openings/closing report as user "0" if enabled in field ∗40.
Default Values
[1]
E
A A
[02]
E
E
A A
[02]
E
E
A A A
[02]
E
E
[08]
E
E
A A A
[04]
E
A A A
[0]
E
A A A
[0]
E
A A A
18