WESTINGHOUSE PACKAGE A/C MANUAL
R-410A : 220V: 60Hz
15. Installation
15.1 Lifting
Rigging cables should have adequate capability to resist 3 times weight of unit. Before lift, please check and
ensure that hooks are holding tightly to unit and lifting angles are no less than 60°.
Cloth material or hard-paper should be padded in the contact place between unit and rigging cable. Rigging
cable should be entwined a round at the hook to forbid danger because of weight unbalance.
During lifting, anyone forbidden lingering under the lifting unit.
15.2 Service Space
1. The recommended clearances for single-unit installations are illustrated in following Fig.
These minimum requirements are not only an important consideration when determining unit placement, but
they are also essential to ensure adequate serviceability, maximum capacity, and peak operating efficiency.
2. Any reduction of the unit clearances indicated in these illustrations may result in condenser coil starvation
or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be
reviewed with a local engineer.
For 6.2ton and above