Specification - Westinghouse WPAXH-060CA4 Service Manual

R-410a; 220volts 60hz
Table of Contents

Advertisement

WESTINGHOUSE PACKAGE A/C MANUAL

6. Specification

Nominal ton
Model
Cooling Capacity (1)
Power Input (1)
Cooling
Cooling Capacity (2)
Power Input (2)
Heating Capacity
Heating
Power Input
Capacity steps
Power supply
Electrical
Max. input consumption
data
Max. current
Indoor fan air flow (High speed)
ESP
Performance
EER 1
EER 2
COP
Number of rows
Fin spacing
Indoor Coil
Tube diameter
Type
Quantity
Diameter(Width)
Indoor fan
Drive type
Motors quantity
Motor model
Motor output
Motor rpm
Type
Quantity
Model
Brand
Compressor
Capacity
Input
Rated current(RLA)
Refrigerant oil charge
(Ton)
5
WPAXH-060CA4
Btu/h
59000
kW
17
kW
5.6
Btu/h
51200
kW
15
kW
7.5
Btu/h
-
kW
-
kW
-
%
0/100
V/Ph/Hz
220/3/60
kW
8.3
A
28.5
CFM
1970
Pa
70
Btu/h/W
10
Btu/h/W
6.8
Btu/h/W
/
4
mm
1.6
inch
1/16''
mm
7.94
inch
5/16''
FC centrifugal
1
mm
282
inch
11.1
Direct
1
YDK600-6E
kW
0.6
r/min
1004
Scroll
1
ZP57K3E-TF5-522
Copeland
Btu/h
58000
kW
5.5
A
22.9
ml
1656
R-410A : 220V: 60Hz
7.5
7.5
WPAXH-090CA4
WPAPH-090CA4
89000
89000
26
26
9.2
9.2
74500
74500
21.8
21.8
9.9
9.9
-
102400
-
30
-
10
0/100
0/100
220/3/60
220/3/60
13.2
13.7
42
45
3000
3000
60
60
9.7
9.7
7.3
7.3
/
10.2
2
2
1.6
1.6
1/16''
1/16''
7.94
7.94
5/16''
5/16''
FC centrifugal
FC centrifugal
1
1
254
254
10
10
Belt
Belt
1
1
YFD90L-4
YFD90L-4
2
2
1120
1120
Scroll
Scroll
1
1
SH090A3ALC
SH090A3ALC
Danfoss
Danfoss
92465
92465
8.569
8.569
30.7
30.7
3000
3000
9