Error Code; Error Code For 5Ton; Error Code For 7.5 Ton And Above - Westinghouse WPAXH-060CA4 Service Manual

R-410a; 220volts 60hz
Table of Contents

Advertisement

WESTINGHOUSE PACKAGE A/C MANUAL

17. Error Code

17.1 Error Code for 5ton

Type
Content
Normal
Standby
Normal
Constraint cooling
Normal
Running
Error
Compressor phase sequence error or phase default
Error
Outdoor coil temp. sensor T3-1 default
Error
Outdoor coil temp. sensor T3-2 default
Error
Indoor coil temp. sensor T2-1 default
Error
Indoor coil temp. sensor T2-2 default
Error
Indoor temp. sensor T1 error
Error
Outdoor ambient temp. sensor T4 error
Error
Wired controller output error
Protection
Over current protection
Protection
Comprehensive protection for outdoor fan
Protection
Protection for High/Low Pressure or exhaust temp. (System 1)
Protection
Protection for High/Low Pressure or exhaust temp. (System 1)
Protection
Protection for High temperature of the outdoor condenser

Error code for 7.5 ton and above

Type
Content
Normal
Standby
Normal
Constraint cool
Normal
Running
Error
Compressor phase sequence error or phase default
Error
Outdoor coil temp. sensor in sys. A error
Error
Outdoor coil temp. sensor in sys. B error
Error
Indoor coil temp. sensor in sys. A error
Error
Indoor coil temp. sensor in sys. B error
Error
Indoor temp. sensor error
Error
Outdoor ambient temp. sensor error
Error
Wired controller output error
Protection
Over-current protection in sys. A
Protection
Over-current protection in sys. B
Protection
Over-current protection for indoor fan
Protection
Comprehensive protection for outdoor fan
Protection
Protection for High/Low Pressure or exhaust temp. in sys. A
Protection
Protection for High/Low Pressure or exhaust temp. in sys. B
Protection
T2 evaporator Hi-temperature protection stop outdoor unit fan
Protection
T2 evaporator Hi- temperature protection then stop outdoor unit fan and compressor
Protection
Protection for condenser Hi-temp. in sys. A
Protection
Protection for condenser Hi-temp. in sys. B
Protection
Anti-freezing protection for evaporator in sys. A
Protection
Anti-freezing protection for evaporator in sys. B
Protection
Defrosting
104
R-410A : 220V: 60Hz
Code
Remarks
--
On
10.
E0
Manual reset
E1
Manual reset
E2
Manual reset
E5
Manual reset
E6
Manual reset
E9
Manual reset
EA
Manual reset
Eb
Manual reset
P0
Auto reset
P3
Auto reset
P4
Auto reset
P5
Auto reset
P8
Auto reset
Code
Remarks
--
On
10.
E0
Manual reset
E1
Manual reset
E2
Manual reset
E5
Manual reset
E6
Manual reset
E9
Manual reset
EA
Manual reset
Eb
Manual reset
P0
Auto reset
P1
Auto reset
P2
Auto reset
P3
Auto reset
Comprehensive protection in sys. A
P4
P5
Comprehensive protection in sys. B
Auto reset
P6
P7
Auto reset
Auto reset
P8
P9
Auto reset
Auto reset
Pc
Pd
Auto reset
Auto reset
dF