Terminal Matching Table; Main Circuit Terminals - YASKAWA V1000 Replacing Manual

Procedure for replacing the v1000 with the ga500
Hide thumbs Also See for V1000:
Table of Contents

Advertisement

3. Terminal Matching Table

Carefully note that some terminals are different in size and shape between the V1000 and GA500. (See Section 3-4.)
Also, all the GA500 model types use European terminals not only in the control circuit but also in the main circuit.
Table 5: Main Circuit Terminal Matching Table

Main Circuit Terminals

V1000
V2A
GA50
0001-0069
2001-2089
V4A
GA50
0001-0038
4001-4060
R/L1
R/L1
S/L2
S/L2
T/L3
T/L3
U/T1
U/T1
V/T2
V/T2
W/T3
W/T3
B1
B1
B2
B2
+1
+1
+2
+2
-
-
(2 pcs)
(2 pcs)
* The single-phase 200V-class GA500 model types are not equipped with the DC reactor connection terminals (+2).
GA500
GA50
B001-B018
For main circuit power supply input
L
N
U/T1
V/T2
For drive output
W/T3
B1
For connecting braking resistor/braking resistor unit
B2
For DC reactor connection, for direct-current power supply input (positive
+1
terminal)
For DC reactor connection
For direct-current power supply input (negative terminal), for braking unit
-
connection (negative terminal)
For grounding: 200 V class, D class grounding (ground to 100 Ω or less)
(2 pcs)
Notes
400 V class: C class grounding (ground to 10 Ω or less)
VAN-V19001E [V1000→GA500]
6/35