Using the Timer Function

Multi-function contact input terminals S3 to S8 can be designated as timer function input terminals, and multi-
function output terminals M1-M2, P1-PC, and P2-PC can be designated as timer function output terminals. By
setting the delay time, you can erase chattering from the sensors and switches.
Set one of the constants H1-01 to H1-06 (multi-function contact input terminal S3 to S8) to 18 (timer func-
tion input).
Set H2-01 to H2-03 (multi-function output terminals M1-M2, P1-PC, and P2-PC function selection) to 12
(timer function output).
Related Constants
Con-
Name
stant
Number
Sets the timer function output
ON-delay time (dead band) for
Timer func-
the timer function input, in 1-
b4-01
tion ON-
second units.
delay time
Enabled when a timer function
is set in H1-
Sets the timer function output
OFF-delay time (dead band) for
Timer func-
the timer function input, in 1-
b4-02
tion OFF-
second units.
delay time
Enabled when a timer function
is set in H1-
Setting Example
When the timer function input ON time is longer than the value set in b4-01, the timer output function is
turned ON. When the timer function input OFF time is longer than the value set in b4-02, the timer output
function is turned OFF. An example of timer function operation is given in the following diagram.
Timer function input
Timer function output
Setting
Description
Range
0.0 to
300.0
or H2-
.
0.0 to
300.0
or H2-
.
Fig 6.61 Timer Function Operation Example
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vec-
tion
PG
0.0 s
No
A
A
0.0 s
No
A
A
Individual Functions
MEMO
BUS
Flux
Regis-
Vec-
ter
tor
tor
A
A
1A3H
A
A
1A4H
107
6-