CHANNEL SELECTION
This control may be operated in 3 different
sub-channels for applications where 2.4GHz
interference causes delayed operation of the
remote control. The factory default is Channel
3. To change the channel on the transmitter:
Touch the CHANNEL PROGRAM and
CHANNEL UNLOCK zones simultane-
ously and hold for 5-seconds.
The LCD screen will go blank except
"Ch" will be displayed in the SET TEMP
Zone and either "01", "02", or "03" will
be displayed in the ROOM TEMP Zone.
Press the UP or DOWN buttons to
change the channel number (01-03).
Press the MODE/SET Button to return
to the normal operating display.
Receiver Operation Notes:
The receiver manufacturer may refer to
channels 01, 02, or 03.
Receiver must be paired with transmitter
in the receiver's factory default channel.
Once paired, the channel selection may
be changed in the transmitter per the
instructions above.
Once the channel selection is changed in
the transmitter, the power supply to the
receiver must be removed for at least
30-seconds, then re-applied.
The receiver will recognize the new
channel selection after about 30-sec-
onds to 1-minute and normal operation
will resume.
MODES OF OPERATION
OPERATION MODES:
MANUAL OFF
MANUAL ON
THERMOSTAT (with optional PRO-
GRAM Mode)
The modes may be cycled in the order above
by touching the MODE Zone or pressing the
MODE/SET Button.
MANUAL OFF MODE:
Transmits fl ame OFF command.
Pilot Method: Intermittent Pilot Ignition
(IPI)/Spark-to-Pilot only (continuous/
standing pilot not allowed)
Pilot fl ame will be turned OFF
26
OPERATION
Continued
LCD Displays:
• MODE Zone: OFF is displayed
• ROOM TEMP Zone: Measured tempera-
• SET TEMP Zone: Blank
• TIME/PROG Zone: Current day indica-
tor and current time is displayed
• FLAME Zone: Blank
MANUAL ON MODE:
Transmits fl ame ON command.
Pilot Method: Intermittent Pilot Ignition
(IPI)/Spark-to-Pilot only (continuous/
standing pilot not allowed)
• Pilot fl ame will be ignited before turn
Main Flame ON.
LCD Displays:
• MODE Zone: ON is displayed
• ROOM TEMP Zone: Measured tempera-
ture is displayed
• SET TEMP Zone: Blank
• TIME/PROG Zone: Current day indicator
and current time is displayed
• FLAME Zone: A Flame Icon and fl ame
setting level number is displayed
THERMOSTAT MODE:
Will cycle fl ame on and off based on
room and set temperatures. Will transmit
ON command if SET TEMP (+SWING)
is higher than ROOM TEMP and will
transmit OFF command if SET TEMP
(-SWING) is lower than ROOM TEMP.
Built-in thermostat will measure room
temperature.
All programming should be written for
deg. F and converted to deg. C when
selected.
Temperatures may be displayed in
degrees F (factory default) or degrees
C. Press the UP and DOWN Buttons
simultaneously to change between
degrees F and C.
SET TEMP: While in THERMOSTAT
mode, press the UP or DOWN Button
to change the SET TEMP (45-90 deg. F,
7-32 deg. C); the new set temperature
will automatically be accepted after 2
seconds. The factory default SET TEMP
is 68 deg. F.