Fault codes
(cont.)
Fault code
Const.
displayed
9C
X
9E
X
9F
X
A3
A4
A7
b0
X
b1
X
b5
X
b7
X
b8
X
bA
bb
Weather-
System characteris-
comp.
tics
X
No solar DHW heat-
ing
X
Control mode
X
Control mode
X
Burner blocked
X
Control mode
X
Control mode as per
delivered condition
X
Burner blocked
X
Control mode as per
delivered condition
X
Control mode as per
delivered condition
X
Burner blocked
X
Burner blocked
X
Mixer regulates to
20 °C flow tempera-
ture.
X
Mixer regulates to
20 °C flow tempera-
ture.
Cause
Measures
Lead break, cylin-
Check temperature sen-
der temperature
sor
%
sensor
module or sensor on the
Vitosolic.
No flow rate in so-
Check solar circuit pump
lar circuit or flow
and solar circuit. Acknowl-
rate too low, or
edge fault message.
temperature limiter
has responded
Solar control mod-
Replace solar control
ule or Vitosolic fault
module or Vitosolic
Flue gas tempera-
Fit flue gas temperature
ture sensor incor-
sensor correctly (see
rectly positioned
page 88).
Max. system pres-
Check system pressure
sure exceeded
max. 3 bar (0.3 MPa)
Check the function and
sizing of the diaphragm
expansion vessel.
Vent the heating system.
Programming unit
Replace programming
faulty
unit
Short circuit, flue
Checking flue gas tem-
gas temperature
perature sensor
sensor
Communication er-
Checking connections
ror, programming
and replacing program-
unit
ming unit if required
Internal fault
Replacing the control unit
Coding card fault
Plug in coding card or re-
place if faulty
Lead break, flue
Checking flue gas tem-
gas temperature
perature sensor
sensor
Communication er-
Check extension kit con-
ror, extension kit
nections and code.
for heating circuit 2
(with mixer)
Communication er-
Check extension kit con-
ror, extension kit
nections and code.
for heating circuit 3
(with mixer)
Troubleshooting
on solar control
79