Check The Fuse; Mixer Extension Kit - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Table of Contents

Advertisement

Maintenance
(cont.)

Check the fuse

A
Fig. 49
1. Switch off the power.
2. Release the side closures and pivot the control unit
down.

Mixer extension kit

Checking the setting of rotary selector S1
The rotary selector on the PCB of the extension kit
defines the assignment to the relevant heating circuit.
Heating circuit
Heating circuit with mixer M2
(heating circuit 2)
Heating circuit with mixer M3
(heating circuit 3)
Checking the rotational direction of the mixer
motor
After being switched on, the boiler implements a self-
test. During this, the mixer is opened and closed again.
F1
3. Remove cover
4. Check fuse F1 (see connection and wiring dia-
Note
The mixer motor can also be started via the actuator
test (see chapter "Checking outputs").
Observe the rotational direction of the mixer motor dur-
ing its self-test.
Rotary selector S1
Then manually set the mixer back to "Open".
setting
The flow temperature sensor must now capture a
2
higher temperature. If the temperature drops, either
the motor is turning in the wrong direction or the mixer
4
insert is incorrectly fitted.
.
A
gram).
Mixer installation instructions
Troubleshooting
89

Advertisement

Table of Contents
loading

Table of Contents