Hardware Configuration - Siemens Simantic ET200SP System Manual

Table of Contents

Advertisement

3.3

Hardware configuration

Maximum mechanical configuration
As soon as one of the following rules applies, the maximum configuration of the ET 200SP
has been reached:
Table 3- 3
Properties
Number of modules
Number of motor starters
Backplane bus length of the
ET 200SP
Electrical maximum configuration for I/O modules
The number of operable I/O modules of a potential group is limited by the following factors:
● Power consumption of the I/O modules
● Power consumption of the components supplied via these I/O modules
The maximum current carrying capacity of the terminals on the BaseUnit L+/M is 10 A.
Current carrying capacity refers to the current load via the power bus and the infeed bus of
the ET 200SP station. Consider the current carrying capacity when using a motor starter.
Maximum electrical configuration for motor starter power bus (24 V DC)
To determine the current requirement of an individual motor starter via the power bus, take
account of the following parameters:
● Current consumption via DC infeed in the ON state
● Current consumption via DC infeed when switching on (40 ms peak load)
● Increased power consumption through fan operation
● Current requirement via encoder supply of the connected DI module
The maximum current carrying capacity of the 24 V potential group is 7 A across the entire
permissible temperature range.
Distributed I/O system
System Manual, 12/2016, A5E03576849-AG
Maximum mechanical configuration
Rule
Maximum of 12/30/32/64 I/O modules (depending on the CPU
used/the interface module used; see CPU
(http://support.automation.siemens.com/WW/view/en/9046643
9/133300) and interface module
(http://support.automation.siemens.com/WW/view/en/5568331
6/133300) manuals)
For every 6 F-modules F-RQ 1x24VDC/24..230VAC/5A
(6ES7136-6RA00-0BF0), the maximum configuration is re-
duced by 1 module.
Maximum of 31 motor starters
maximum 1 m mounting width (without CPU/interface module,
including server module)
Application planning
3.3 Hardware configuration
41