Technical data
6.1 Input
Integrated input fuse
Protection in the line feeder
cable (IEC 898)
Figure 6-1
38
6EP3333-8SB00-0AY0
(24 V/5 A)
Fuse
T 3.15 A
Recommended: Miniature
circuit breaker (IEC 898),
characteristic C, 6 A
Power failure buffering
6EP3334-8SB00-0AY0
(24 V/10 A)
Fuse
T 6.3 A
Recommended: Miniature
circuit breaker (IEC 898),
characteristic C, 10 A
Manual, 11.2014, C98130-A7633-A1-3-7629
6EP1336-3BA10
(24 V/20 A)
Fuse
T 10 A
Recommended miniature
circuit breaker for single-
phase operation: 10 A, char-
acteristic C; required for two-
phase operation: Miniature
circuit breaker, two-pole
coupled or circuit breaker (8
or 4 A) according to UL 489:
3RV2711-1HD10 (120 V) or
3RV2711-1ED10 (230 V)