Siemens SITOP PSU8200 Manual page 15

1ph
Hide thumbs Also See for SITOP PSU8200:
Table of Contents

Advertisement

Operating display
Signaling contact
Figure 2-7
Signaling
LED green (4.1) off
Signaling contact (5), contacts 13-14 open
(quiescent position)
Green LED (4.1) lit
Signaling contact (5), contacts 13-14 closed
Yellow LED (4.2) lit
Signaling contact (5), contacts 13-14 open
(quiescent position)
Red LED (4.3) lit
Signaling contact (5), contacts 13-14 open
(quiescent position)
SITOP PSU8200 1ph
Manual, 11.2014, C98130-A7633-A1-3-7629
6EP1336-3BA10 (24 V/20 A)
LED green, lit for "24 V O.K."
Yellow LED lit for overload condition (Ua <20 V ±0.5 V)
Red LED lit for latching shutdown as a result of overload
(only for selector switch B in the "ON" position)
Relay contact (NO contact, contact rating 30 V AC/0.5 A, 30 V DC/1 A) for
"24 V O.K."
Operating display and signaling contact for 6EP1336-3BA10
Description, device design, dimension drawing
2.4 Status displays and signaling
6EP1336-3BA10 (24 V/20 A)
No supply voltage
Normal operation, output voltage >20 V ±0.5 V
Overload (U
<20 V ±0.5 V)
a
Latching shutdown due to overload
15