Potterton Paramount four Installation Manual page 72

30-115 kw
Table of Contents

Advertisement

9 Settings
Configuration of extension modules
Input value 1 H21 module 1
Funct value 1 H21 module 1
Input value 2 H21 module 1
Funct value 2 H21 module 1
Funct input EX21 module 1
None | Temperature monitor HC
Funct output UX21 module 1
None | Boiler pump Q1 | Hot water pump Q3 | HW interm circ pump Q33 | Heat­
ing pump CH1 Q2 | Heating pump CH2 Q6 | Heating pump CH3 Q20 | Collector
pump Q5 | Solar pump ext exch K9 | Solar pump buffer K8 | Solar pump swi
pool K18
Signal output UX21 module 1
10 V | PWM
Funct output UX22 module 1
See
Parameters see Funct output UX21 module 1 (prog. no.
7348)!
Signal output UX22 module 1
10 V | PWM
Function extension module 2
None | Multifunctional | Temps / mode CH1 | Temps / mode CH2 |Temps /
mode CH3 | Solar HW | Primary contr/system pump
Relay output QX21 module 2
None | Circulating pump Q4 | El imm heater HW K6 | Collector pump Q5 | Cons
circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 | heating pump CH3
Q20 |Cons circuit pump VK2 Q18 | System pump Q14 | Heat gen shutoff valve
Y4 | Solid fuel boiler pump Q10 | Time setting 5 K13 | Buffer return valve Y15 |
Solar pump ext exch K9 | Solar ctrl elem buffer K8 | Solar ctrl elem swi pool K18
| Swimming pool pump Q19 | Cascade pump Q25 | St tank transfer pump Q11 |
Hot water mixing pump Q35 | HW interm circ pump Q33 | Heat request K27 |
heating pump CH1 Q2 | heating pump CH2 Q6 | Hot water ctrl elem Q3 | Status
output K35 | Status information K36 | Fan shutdown K38
Relay output QX22 module 2
See
Parameters see Relay output QX21 module 2 (prog. no.
7376)!
Relay output QX23 module 2
See
Parameters see Relay output QX21 module 2 (prog. no.
7376)!
Sensor input BX21 module 2
See
Parameters see Sensor input BX21 module 1 (prog. no.
7307)!
Sensor input BX22 module 2
See
Parameters see Sensor input BX21 module 1 (prog. no.
7307)!
Function input H2 module 2
See
Parameters see Function input H2 module 1 (Prog. no. 7311)!
Contact type H2 module 2
NC | NO
72
Paramount four 30 – 115 kW
Prog. no.
Level
Standard value
7324
E
0
7325
E
0
7326
E
10
7327
E
100
7342
C
None
7348
E
None
7350
E
PWM
7355
E
None
7357
E
PWM
7375
C
None
7376
C
None
7377
C
None
7378
C
None
7382
C
None
7383
C
None
7386
C
None
7387
C
NO
7658013 - 02 - 15092016

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents