Configuration
Hot water separate circuit
Off | On
Optg action HW div valve
Position on CH | Position on HW
Ctrl boiler pump/HW valve
All requests | Request CH1/HW only
Boiler pump at DHW
Off | On
Solar controlling element
Charging pump | Diverting valve
External solar exchanger
Commonly | Hot water storage tank | Buffer storage tank
Combi storage tank
No | Yes
Relay output QX1
None | Circulating pump Q4 | El imm heater HW K6 | Collector pump Q5 | Cons
circuit pump VK1 Q15 | Boiler pump Q1 | Alarm output K10 | heating pump CH3
Q20 | Cons circuit pump VK2 Q18 | System pump Q14 | Heat gen shutoff valve
Y4 | Solid fuel boiler pump Q10 | Time setting 5 K13 | Buffer return valve Y15 |
Solar pump ext exch K9 | Solar ctrl elem buffer K8 | Solar ctrl elem swi pool K18
| Swimming pool pump Q19 | Cascade pump Q25 | St tank transfer pump Q11 |
Hot water mixing pump Q35 | HW interm circ pump Q33 | Heat request K27 |
heating pump CH1 Q2 | heating pump CH2 Q6 | Hot water ctrl elem Q3 | Status
output K35 | Status information K36 | Flue gas damper K37 | Fan shutdown K38
Relay output QX2
See
Parameters see Relay output QX1 (prog. no. 5890)!
Relay output QX3
See
Parameters see Relay output QX1 (prog. no. 5890)!
Sensor input BX1
None | Hot water sensor B31 | Collector sensor B6 |HW circulation sensor B39 |
Buffer sensor B4 | Buffer sensor B41| Common flow sensor B10 | Solid fuel
boiler sensor B22 |HW charging sensor B36 |Buffer sensor B42 | Common
return sensor B73 | Cascade return sensor B70 | Swimming pool sensor B13 |
Solar flow sensor B63 | Solar return sensor B64
Sensor input BX2
See
Parameters see Sensor input BX1 (prog. no. 5930)!
Sensor input BX3
See
Parameters see Sensor input BX1 (prog. no. 5930)!
None | Hot water sensor B31 | Collector sensor B6 | HW charging sensor B36
Function input H1
None | Optg mode change CHs+HW | Optg mode changeover HW | Optg mode
changeover CHs | Optg mode changeover CH1 | Optg mode changeover CH2 |
Optg mode changeover CH3 | Heat generation lock | Error/alarm message |
Consumer request VK1 | Consumer request VK2 | Release swimpool source
htg | Excess heat discharge | Release swi pool solar | Operating level HW |
Operating level CH1 | Operating level CH2 | Operating level CH3 | Room
thermostat CH1 | Room thermostat CH2 | Room thermostat CH3 | Hot water
thermostat | Pulse count | Checkb sign flue gas damper | Start prevention |
Consumer request VK1 10V | Consumer request VK2 10V | Preselected output
10V
7658013 - 02 - 15092016
Prog. no.
Level
Standard value
5736
E
Off
5737
E
Position on CH
5774
E
All requests
5775
E
On
5840
E
Diverting valve
5841
E
Commonly
5870
E
No
5890
C
None
5891
C
None
5892
C
Hot water ctrl elem
Q3
5930
C
Collector sensor B6
5931
C
Hot water sensor
B31
5932
C
Buffer sensor B4
5950
C
None
Paramount four 30 – 115 kW
9 Settings
67