Potterton Paramount four Installation Manual page 63

30-115 kw
Table of Contents

Advertisement

Boiler
Fan output heating max
(1)
Fan output full charging max
(1)
Fan output DHW max
Controller delay
Off | Heating mode only | Hot water mode only | Heating and HW mode
Controller delay fan output
Controller delay duration
Switching diff on CHs
Switching diff off min CHs
Switching diff off max CHs
Switching diff on HW
Switching diff off min HW
Switching diff off max HW
Delay heat req special op
Pressure switch shutdown
Start prevention | Lockout position
Gas energy metering
Off | On
Gas energy metering correction
(1) The kW settings are approximate values. Exact values can be determined by the gas meter for example.
7658013 - 02 - 15092016
(1)
(1)
Prog. no.
Level
Standard value
2441
E
Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
2442
E
Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
2444
E
Paramount four 30:
30 kW; Paramount
four 40: 38 kW
Paramount four 50:
50 kW; Paramount
four 60: 58 kW; Para‐
mount four 80: 77 kW;
Paramount four 95:
95 kW; Paramount
four 115: 115 kW
2450
E
Heating mode only
2452
E
Paramount four 30:
10,0 kW; Paramount
four 40: 14.0 kW
Paramount four 50:
20,0 kW; Paramount
four 60: 22,5 kW; Pa‐
ramount four 80: 34,5
kW; Paramount four
95: 36,0 kW; Para‐
mount four 115: 40.0
kW
2453
E
40 s
2454
E
4 °C
2455
E
5 °C
2456
E
10 °C
2460
E
5 °C
2461
E
6 °C
2462
E
8 °C
2470
E
0 s
2500
E
Start prevention
2550
C
Off
2551
C
1.0
Paramount four 30 – 115 kW
9 Settings
63