Potterton Paramount four Installation Manual page 65

30-115 kw
Table of Contents

Advertisement

Solid fuel boiler
Locks other heat sources
Off | On
Setpoint min
Temp diff on
Temp diff off
Comparative temp
Hot water sensor B3 | Hot water sensor B31 | Buffer sensor B4 | Buffer sensor
B41 | Flow temp setpoint | Setpoint min
Pump overrun time
Buffer storage tank
Auto generation lock
None | With B4 | With B4 and B42/B41
Auto heat gen lock SD
Temp diff buffer/CH
Min st tank temp heat mode
Charging temp max
Recooling temp
Recooling HW/CHs
Off | On
Recooling collector
Off | Summer | Always
With solar integration
No | Yes
Temp diff on return div
Temp diff off return div
Compar temp return div
With B4 | With B41 | With B42
Optg action return diversion
Temp decrease | Temp increase
Full charging
Off | Heating mode | Always
Full charging temp min
Full charging sensor
With B4 | With B42/B41
Domestic water storage tank
Forward shift charging
Flow setpoint boost
Transfer boost
Type of charging
Recharging | Full charging | Full charging legio | Full charg 1st time day | Full
charg 1st time legio
Switching diff
Charging time limitation
Discharging protection
Off | Always | Automatically
Charging temp max
Recooling temp
7658013 - 02 - 15092016
(1)
Prog. no.
Level
Standard value
4102
E
Off
4110
E
65 °C
4130
E
8 °C
4131
E
4 °C
4133
E
Buffer sensor B41
4140
E
20 min
Prog. no.
Level
Standard value
4720
E
With B4
4721
E
5 °C
4722
E
-3 °C
4724
E
- - - °C
4750
E
80 °C
4755
E
60 °C
4756
E
Off
4757
E
Off
4783
E
Yes
4790
E
8 °C
4791
E
4 °C
4795
E
With B4
4796
E
Temp increase
4810
E
Off
4811
E
8 °C
4813
E
With B42/B41
Prog. no.
Level
Standard value
5011
E
60 min
5020
E
18 °C
5021
E
10 °C
5022
E
Full charging
5024
E
4 °C
5030
E
120 min
5040
E
Automatically
5050
E
69 °C
5055
E
80 °C
Paramount four 30 – 115 kW