9 Settings
116
Paramount four 30 – 115 kW
Note
The time is only counted, when the maintenance message has
been activated.
Fan speed ionization current (7050)
Speed limit from which the ionisation current service alarm should be set
(prog. no. 7051), if the ionisation current monitoring and therefore a speed
increase based on too low ionisation current active is.
Message ionization current (7051)
Function for display and reset of the burner ionization current maintenance
message. The maintenance message can only be reset if the reason for
maintenance has been eliminated.
Chimney sweep function (7130)
The chimney sweep function is switched on or off under this prog no.
Note
The function is switched off by the settingOff or automatically if the
maximum boiler temperature is reached.
It can also be directly activated via the chimney sweep button.
Manual control (7140)
Activation of manual control. If the manual control function is activated the
boiler is controlled to the setpoint manual control. All the pumps are
switched on. Additional request will be ignored!
Controller stop function (7143)
If the controller stop function is activated, the burner output set in the set­
point controller stop is directly requested by the device.
Controller stop setpoint (7145)
With activated controller stop function the output set here is requested by
the device.
Compulsory heat draw-off DHW (7165)
This parameter is used to set that heat pumping to the domestic hot water
circuit takes priority when the chimney sweep function is active.
Off: Compulsory pumping of the heat to the heating circuits.
On: When the chimney sweep function is active, heat is pumped with
priority into the domestic hot water circuit.
Telephone customer service (7170)
Here the desired telephone number of customer service can be entered.
PStick storage pos (7250)
The parameterPStick storage pos can be used to select the data set (data
set number on the stick) to be written or read.
PStick Des Data set (7251)
If a data set is selected under prog. no. 7250, the name of the data set is
displayed under prog. no 7251. For backup sticks the data set name is dis­
BUYYMMDDHHMM (BU for backup and date of back­
played in the format
up: Year, Month, Day, Hour, Minute). As soon as a data set number is se­
lected, the text is displayed for the data set description.
PStick command (7252)
No operation: This is the basic state. As long as no operation is active
on the stick, this command is displayed.
Reading from stick: Starts reading the data from the stick. This operation
is only possible with READ sticks. The data of the set data set is copied
to the LMS control. First a check is carried out as to whether the data
set may be imported. If the data set is incompatible, it must not be im­
ported. The display resets toNo operation and displays an error mes­
sage. The textReading from stick remains until the operation is comple­
ted or an error occurs. As soon as data transmission begins, the LMS