9 Settings
Domestic water storage tank
Recooling collector
Off | Summer | Always
El imm heater optg mode
Substitute | Summer | Always
El immersion heater release
24h/day | Hot water release | Time hot water
El immersion heater control
External thermostat | Hot water sensor
Hot water boost
Off | On
Excess heat draw
Off | On
With buffer
No | Yes
With prim contr/system pump
No | Yes
With solar integration
No | Yes
Pump speed min
Pump speed max
Speed Xp
Speed Tn
Speed Tv
Transfer strategy
Always | Hot water release
Interm circ boost recharging
Intermediate circuit boost
Excess interm circ temp max
Flow setp compensation delay
Flow setp compensation Xp
Flow setp compensation Tn
Flow setp compensation Tv
Full charging with B36
No | Yes
Min start temp diff Q33
Excess interm circ temp del
(1) Parameters depend on the hydraulic System!
Configuration
Temps / mode CH1
Off | On
Temps / mode CH2
Off | On
Temps / mode CH3
Off | On
Hot water sensor
Hot water sensor B3 | Thermostat
Hot water ctrl elem Q3
No charging request | Charging pump | Diverting valve
Basic pos HW div valve
Last request | Central heating | Hot water
66
Paramount four 30 – 115 kW
(1)
Prog. no.
Level
Standard value
5057
E
Off
5060
E
Substitute
5061
E
Hot water release
5062
E
Hot water sensor
5070
E
On
5085
E
On
5090
E
Yes
5092
E
Yes
5093
E
Yes
5101
E
0 %
5102
E
100 %
5103
E
35 °C
5104
E
120 s
5105
E
45 s
5130
E
Always
5139
E
5 °C
5140
E
2 °C
5141
E
2 °C
5142
E
30 s
5143
E
60 °C
5144
E
30 s
5145
E
30 s
5146
E
No
5148
E
-3 °C
5151
E
30 s
Prog. no.
Level
Standard value
5710
C
On
5715
C
Off
5721
C
Off
5730
E
Hot water sensor B3
5731
E
Charging pump
5734
E
Central heating
7658013 - 02 - 15092016