Siemens simatic S7-1500 Manual page 32

Digital outpoot module
Hide thumbs Also See for simatic S7-1500:
Table of Contents

Advertisement

Technical specifications
Residual current at signal state "0":
Note
Due to the Diagnostics: Wire break function, there is a low level of residual current in the "0"
signal state at the output, which may cause the display diodes to flicker.
This residual current does not depend on the setting for the wire break diagnostics
parameter.
Power reduction (derating) to aggregate current of outputs (per group)
The following graphs show the loading capacity of the digital outputs in relation to the
mounting position of the S71500 / Distributed I/O System ET 200MP automation system and
the ambient temperature.
Figure 6-1
32
Horizontal mounting of the system
Vertical mounting of the system
Details on aggregate current of outputs (per group)
Digital output module DQ 32x24VDC/0.5A HF (6ES7522-1BL01-0AB0)
Manual, 09/2016, A5E35683508-AB

Hide quick links: