Technical specifications
Digital outputs
Number of outputs
Sourcing output
Short-circuit protection
Limitation of inductive shutdown voltage to
Control of a digital input
Switching capacity of outputs
With resistive load, max.
With lamp load, max.
Load resistance range
Low limit
High limit
Output voltage
For signal "1", min.
Output current
For signal "1" rated value
For signal "1" permitted range, max.
For signal "0" residual current, max.
Output delay with resistive load
"0" to "1", max.
"1" to "0", max.
Parallel connection of two outputs
For logic operations
For increased performance
For redundant control of a load
Switching frequency
With resistive load, max.
With inductive load, max.
With lamp load, max.
Total current of outputs
Current per channel, max.
Current per group, max.
Current per module, max.
Cable length
shielded, max.
unshielded, max.
Isochronous mode
Isochronous mode (application synchronized up to
terminal)
Execution and activation time (TCO), min.
Bus cycle time (TDP), min.
30
Response threshold, typ.
32
Yes
Yes; electronic clocking
1 A
L+ (-53 V)
Yes
0.5 A
5 W
48 Ω
12 kΩ
L+ (-0.8 V)
0.5 A
0.5 A
0.5 mA
100 µs
500 µs
Yes
No
Yes
100 Hz
0.5 Hz; according to IEC 60947-5-1, DC-13
10 Hz
0.5 A; see additional description in the manual
4 A; see additional description in the manual
16 A; see additional description in the manual
1000 m
600 m
Yes
70 µs
250 µs
Digital output module DQ 32x24VDC/0.5A HF (6ES7522-1BL01-0AB0)