Siemens simatic S7-1500 Manual page 17

Digital outpoot module
Hide thumbs Also See for simatic S7-1500:
Table of Contents

Advertisement

For parameter assignment in the user program, the parameters are transferred to the
module using the WRREC instruction (parameter assignment in RUN) and data records; see
chapter Parameter assignment and structure of the parameter data records (Page 35).
Table 4- 1
Configurable parameters and their defaults
Parameters
Range of values
Diagnostics
Yes/No
Missing sup-
ply voltage L+
Yes/No
Short circuit
to ground
Yes/No
Wire break
Reaction to CPU
Turn off
STOP
Keep last value
Output substitute value 1
* If you enable diagnostics for multiple channels, you will receive an alarm surge on failure of the supply voltage because
each enabled channel will detect this fault.
You can prevent this message burst by assigning the diagnostics function to one channel only.
Digital output module DQ 32x24VDC/0.5A HF (6ES7522-1BL01-0AB0)
Manual, 09/2016, A5E35683508-AB
Default
Parameter
setting
assignment
in RUN
No
Yes
No
Yes
No
Yes
Turn off
Yes
Parameters/address space
Scope with configuration software, e.g.,
STEP 7 (TIA Portal)
Integrated in the
GSD file
hardware catalog
PROFIBUS DP
as of STEP 7, V13
SP1 or GSD file
PROFINET IO
Channel*
Channel group
(CH0 to CH7, CH8 to
CH15,
(CH16 to CH23,
CH24 to CH31)
Channel*
Channel group
(CH0 to CH7, CH8 to
CH15,
(CH16 to CH23,
CH24 to CH31)
Channel*
Channel group
(CH0 to CH7, CH8 to
CH15,
(CH16 to CH23,
CH24 to CH31)
Channel
Channel
4.1 Parameters
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents