Preparation

Step 1.1 Choosing the installation
location
If using a multi system, install as described in the
installation manual supplied with the outdoor unit.
Overview of installation location requirements
125 mm
or more
Drain hose hole
You can select the direction of
draining (left or right).
Maximum pipe height: 8 m
Maximum pipe length: 15 m
Make at least one round to
reduce noise and vibration.
The actual units may look different from
the images depicted here.
Pipe length
Model
Minimum
3
09/12
Outdoor
Unit
Outer wall
Indoor
Unit
Cut insulation to have
rainwater drained
A3050_EU_Best model_IM_DB68-06152A-00_EN.indd 5
100 mm or more
125 mm
or more
(Unit : m)
Pipe height
Maximum
Maximum
15
8
Make a U-trap (A) on the
pipe (which is connected to
the indoor unit) at outer wall
CAUTION
and cut the bottom part of
the insulation (about 10 mm)
to prevent rainwater from
getting inside through the
insulation.
CAUTION
• Comply with the length and height limits described in
the figure above.
Minimum clearances for the outdoor unit
Wall
Minimum clearance in mm
600
Air flow direction
Top view
When installing 1 outdoor unit
(6 cases)
150
600
300
Side view
(Unit: mm)
2000
English
5
2016/4/20 14:10:15