Step 2.7 Optional: Changing The Direction Of The Drain Hose - Samsung AR**HS Installation Manual

Table of Contents

Advertisement

Step 2.7 Optional: Changing the
direction of the drain hose
Pour water in the direction of arrow.
<Front view>
Direction of the drained water
<Side view>
CAUTION
• Make sure that the indoor unit is in upright position
when you pour water to check for leakage. Make sure
that the water does not overflow onto the electrical
part.
A3050_EU_Best model_IM_DB68-06152A-00_EN.indd 13
Step 2.8 Installing and connecting
the assembly pipes to the refrigerant
pipes (assembly pipe)
Connect indoor and outdoor units with field-supplied
Drain pan outlet
copper pipes by means of flare connections. Use insulated
Rubber cap
seamless refrigeration grade pipe only, (Cu DHP type
according to ISO1337), degreased and deoxidized, suitable
for operating pressures of at least 4200 kPa and for burst
pressure of at least 20700 kPa. Under no circumstances
must sanitary type copper pipe be used.
There are 2 refrigerant pipes of different diameters:
• The smaller one is for the liquid refrigerant
• The larger one is for the gas refrigerant
A short liquid refrigerant pipe and a short gas refrigerant
pipe are already fitted to the air conditioner. The
connection procedure for the refrigerant pipes varies
according to the exit position of each pipe when facing
the wall:
Left(A)
2 <Assembling the
hanger screw>
1
Cut out the appropriate knock-out piece (A, B, C) on
the rear of the indoor unit unless you connect the pipe
directly from the rear.
2
Smooth the cut edges.
Right(B)
1 <Front view>
Underside(C)
Guide right
or left
Screw
3 <Side view>
English
2016/4/20 14:10:21
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar**js

Table of Contents