Step 3: Ground the ACX4000 Router

Tools Required to Ground the ACX4000 Router

Connect the Grounding Cable

Copyright © 2015, Juniper Networks, Inc.
You must ground the router before connecting power.
Tools Required to Ground the ACX4000 Router on page 9
Connect the Grounding Cable on page 9
To ground the router, you need the following tools:
Phillips (+) screwdriver, number 2
ESD grounding wrist strap
Two SAE 10-32 screws and paint piercing washers (not provided)
Grounding lug, Panduit LCD06-10-A or equivalent (not provided)
Grounding cable, minimum 6 AWG (13.3 mm
You ground the router by connecting a grounding cable to earth ground and then attaching
it to the chassis grounding points. To ground the router:
Verify that a licensed electrician has attached the cable lug provided with the router
1.
to the grounding cable.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
2.
the strap to an approved site ESD grounding point. See the instructions for your site.
Ensure that all grounding surfaces are clean and brought to a bright finish before
3.
grounding connections are made.
Connect the grounding cable to a proper earth ground.
4.
Detach the ESD grounding strap from the site ESD grounding point.
5.
Attach an electrostatic discharge (ESD) grounding strap to your bare wrist, and connect
6.
the strap to one of the ESD points on the chassis.
Place the grounding cable lug over the grounding points on the front of the chassis
7.
(see
Figure 5 on page
10).
Secure the grounding cable lug with the washers and screws. The holes are sized for
8.
SAE 10-32 screws. Apply 4.34 lb-in (0.49 Nm) of torque to each screw. Do not
overtighten the screw. (Use a number 2 Phillips screwdriver.)
CAUTION:
Ensure that each grounding cable lug seats flush against the
surface of the grounding points as you are tightening the screws. Ensure
that each screw is properly threaded into the grounding points. Applying
installation torque to the screw when improperly threaded may result in
damage to the terminal.
Step 3: Ground the ACX4000 Router
2
) 90° C wire (not provided)
9