Troubleshooting
General Bypass
38
Siemens Industry, Inc.
Problem Description
Drive does not start on closing of the
run command.
Diagnostic Test Points
The diagnostic board provides a centralized location for diagnostics troubleshooting.
The test points on this board make it easier to troubleshoot the bypass components.
Figure 9: Diagnostic Test Points.
BT300 Bypass Operator's Manual
Possible Cause
●
The Siemens BT300 Bypass is not in Drive - Auto Mode.
●
Drive output contactor is not closed.
●
Remote contact is not closed. Replace with jumper to verify.
●
Run relay has failed.
●
Loose control wire connection.
●
The BT300 Drive Digital Input 1 is not programmed properly.