Diagnostic Test Points - Siemens BT300 Operator's Manual

Bypass variable frequency drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Troubleshooting
General Bypass
38
Siemens Industry, Inc.
Problem Description
Drive does not start on closing of the
run command.

Diagnostic Test Points

The diagnostic board provides a centralized location for diagnostics troubleshooting.
The test points on this board make it easier to troubleshoot the bypass components.
Figure 9: Diagnostic Test Points.
BT300 Bypass Operator's Manual
Possible Cause
The Siemens BT300 Bypass is not in Drive - Auto Mode.
Drive output contactor is not closed.
Remote contact is not closed. Replace with jumper to verify.
Run relay has failed.
Loose control wire connection.
The BT300 Drive Digital Input 1 is not programmed properly.
DPD01391
2016-08-05