Operation (Electronic Bypass Only); Drive Mode - Auto - Siemens BT300 Operator's Manual

Bypass variable frequency drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Operation (Electronic Bypass Only)

Drive Mode – Auto
Siemens Industry, Inc.
The drive powers up in Drive mode. In this mode the drive can be controlled normally
from Auto or Hand control place. In the Drive mode the Bypass running relay output
signal is off and the drive's output contactor is energized by closing the relay RO2 on
OPT-B5 board. Bypass contactor is open. A relay output signal Drive active is on when
the drive is in Drive mode.
The Drive mode can be entered from the Bypass mode by pressing the Hand/Auto
button and selecting either Hand or Auto behind the Drive menu.
Mode of operation is the same in both the conventional and electronic bypasses.
However, there are different methods for determining the modes. The procedures in
this section are used to change operational modes.
Auto mode is the default mode of operation.
This mode is used when the drive is to have control of the motor, and the drive is
being used with an automation system.
In Auto mode, the Bypass (M1) contactor is opened and the Output (M2) contactor
is closed.
1.
At the drive keypad, press the Hand/Auto
2.
Use the Up and/or Down Arrow
highlight Drive, and then press OK
3.
Use the Up and/or Down Arrow
highlight Auto, and then press OK
BT300 Bypass Operator's Manual
Operation (Electronic Bypass Only)
Drive Mode – Auto
button.
buttons to
.
buttons to
.
27
DPD01391