Troubleshooting
Bypass-Specific Fault Codes
Table 4: Fault Codes.
Fault Code
Fault ID
80
1080
1180
1280
1380
1480
1580
1680
1780
81
1081
82
1082
General Bypass
Siemens Industry, Inc.
Fault Name
Remote Safety 1
Digital input contact closure is
missing.
Remote Safety 2
N/A
Remote Safety 3
N/A
Remote Safety 4
N/A
Remote Safety 5
N/A
Remote Safety 6
N/A
Remote Safety 7
N/A
Remote Safety 8
N/A
Overload
Overload relay located in bypass
cabinet has triggered.
Bypass Not Possible
The BT300-OPT-B5-V option
board is missing, and Bypass
(P3.17.4) is set to Electronic.
Problem Description
Contactors do not close.
Main input fuses blow when the motor
is run in bypass.
BT300 Bypass Operator's Manual
Possible Cause
Verify the status of the digital input as defined by
Remote Safety 1 (P3.5.1.44).
If not in use, set to a value of DigIN Slot0.2.
Verify the status of the digital input as defined by
Remote Safety 2 (P3.5.1.45).
If not in use, set to a value of DigIN Slot0.2.
Verify the status of the digital input as defined by
Remote Safety 3 (P3.5.1.46).
If not in use, set to a value of DigIN Slot0.2.
Verify the status of the digital input as defined by
Remote Safety 4 (P3.5.1.47).
If not in use, set to a value of DigIN Slot0.2.
Verify the status of the digital input as defined by
Remote Safety 5 (P3.5.1.48).
If not in use, set to a value of DigIN Slot0.2.
Possible Cause
●
Main input circuit protection has opened.
●
Control power fuse has opened.
●
Safety circuit is open.
●
Motor overload must be reset.
●
Loose control wire connection.
The short circuit protection supplied by the factory is
approximately 1.5 times the NEC listed motor current rating.
Some applications and motor characteristics may require up-
sizing this protection. If this is required in the field, ensure that
there is an appropriate match between the types of fuses and
rating with the fuse holder.
Troubleshooting
Bypass-Specific Fault Codes
Possible Remedy
37
DPD01391
2016-08-05