Operation Selection After Cooling Fan Fault - YASKAWA varispeed G7 CIMR-G7B series Instruction Manual

General purpose inverter (advanced vector control)
Table of Contents

Advertisement

Operation Selection After Cooling Fan Fault

Use the constant setting to select the operation of the motor after a cooling fan fault occurs. This function can
be used for times when a motor should not be stopped quickly (with an emergency stop.)
A cooling fan equipped for 200 V Class Inverters of 7.5 kW, 15 kW, and 30 to 110 kW, and 400 V Class
Inverters of 5.5 to 15 kW and 55 to 300 kW.
Related Constants
Name
Con-
stant
Display
Number
OH1 detection
0: Disabled (FAN minor fault
of Inverter' s
L8-32
cooling fan
1: Enabled (OH1 major fault
OH1 检出选择
The following table describes the operation of the motor and the display of the Digital Operator in accordance
with the settings of the L8-32 if a cooling fan fault occurred.
Setting
Fault
Value
Cooling Fin Overheating
0
Inverter's Cooling Fan Fault FAN (blink)
Cooling Fin Overheating
1
Inverter's Cooling Fan Fault OH1 (lit)
* If L8-32 is set to 0, the motor will continue running even if a cooling fan fault occurred. However, the Inverter rated output current and the
overload capacity will be reduced. The rated output current will be reduced to 80% if the normal rated output current is 100%, and the overload
capacity will be reduced to the values as follows.
When CT is selected: 100% per every 3 minutes, 150% per every 15 seconds
When VT is selected: 100% per every 30 seconds, 120% per every 10 seconds
If L8-32 is set to 0, be sure to set H2-01 to H2-03 multi-function contact outputs to 10 (minor fault) or to 3D
(Inverter's cooling fan fault.) If a cooling fan fault occurs, stop the Inverter immediately and replace the cool-
ing fan. If the Inverter continues to run while a cooling fan fault occurs, the Inverter's cooling ability will be
affected and the Inverter's internal temperature will increase and shorten the Inverter's life.
IMPORTANT
During a cooling fan fault, the cooling fan stops for about 3 seconds every minute (interval operation.)
Setting
Description
Range
detection)
0 or 1
detection)
Digital Operator
OH1 (lit)
OH (lit)
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vector
tion
PG
1
No
A
A
Multi-function Con-
Motor Operation
Coast to a stop
Fault
*
Minor fault
Continue operation
Coast to a stop
Fault
Coast to a stop
Fault
Continuing Operation
MEMO
Open
BUS
Flux
Loop
Regis-
Vec-
Vector
ter
tor
1
2
A
4E2H
A
A
tact Output
6-
73