- Check mechanics and pneumatics in the valve
- Compare the specifications in the Transducer Block, which describe the valve as well as
the actuator and the mechanical structure, with the actual valve.
Reinitialize.
Data Integrity Error
Checksum error
Algorithm Error
Set point value - actual value error

8.3 Messages of the SELF_CALIB_STATUS parameter (Transducer Block)

Proportional band restricted too much
Even the smallest permissible pulses still cause excessive changes in travel. Initialization
aborted.
Possible sources of error:
– Supply pressure too high
– Signal pressure throttle missing in actuator with a small volume
– Mechanical failure, especially with attachment according to IEC 60534-6 (NAMUR)
– If a booster valve is mounted with an actuator with a large volume, the bypass should
be opened further.