Samson 3787 Mounting And Operating Instructions page 47

Foundation fieldbus positioner
Table of Contents

Advertisement

Note:
When initialization based on maximum range (default) is selected, the positioner can be
started up directly after being attached to the control valve via the SELF_CALIB_CMD par-
ameter.
The results of the initialization are saved in SELF_CALIB_STATUS. When this type of initializa-
tion is used, other parameters in this block generally do not require any adaptation.
ACT_FAIL_ACTION
Index: 21
Access: r
Display:
ACT_MAN_ID
Index: 22
Access: r, w
ACT_MODEL_NUM
Index: 23
Access: r, w
ACT_SN
Index: 24
Access: r,w
ACT_STROKE_TIME_DEC
Index: 59
Access: r
ACT_STROKE_TIME_INC
Index: 60
Access: r
ACTUATOR_TYPE
Index: 46
Access: r
Display:
ACTUATOR_VERSION
Index: 48
Access: r, w
Input:
Default:
S
Fail-safe position of the actuator when the auxiliary power fails. It is determined
automatically during initialization.
UNINITIALIZED
Not initialized, undefined
SELF-CLOSING
Closing (in direction 0 % position)
SELF-OPENING
Opening (in direction 100 % position)
INDETERMINATE None
S
Manufacturer of actuator
Clearly identifies the manufacturer of the actuator associated with the positioner.
S
Type / version of the actuator associated with the positioner.
S
Serial number of the actuator associated with the positioner.
S
Minimum transit time CLOSED position
The minimum transit time CLOSED (in direction 0 % position) is the actual time in
seconds which the positioner, actuator and valve need to move through the rated
travel/nominal angle to close the valve (measured during initialization).
S
Minimum transit time OPEN position
The minimum transit time OPEN (in direction 100 % position) is the actual time in
seconds which the positioner, actuator and valve need to move through the rated
travel/nominal angle to open the valve (measured during initialization).
N
Type of actuator associated with the positioner.
ELECTRO PNEUMATIC
S
Actuator design with or without spring-return mechanism.
SINGLE ACTING
single acting, with spring-return mechanism
DOUBLE ACTING double acting, without spring-return mechanism
SINGLE ACTING
Parameter description
47