Samson 3787 Mounting And Operating Instructions page 45

Foundation fieldbus positioner
Table of Contents

Advertisement

TEXT_INPUT_3
Index: 52
Access: r,w
UPDATE_EVT
Index: 35
Access: r
WRITE_ALM
Index: 40
Access: r, w
WRITE_LOCK
Index: 34
Access: r, w
Option:
WRITE_PRI
Index: 39
Access: r, w
Input:
Default:
WRITE_PROTECT_SWITCH
Index: 49
Access: r
N
Freely available space for entering text.
D
This alert is generated by any change to the static data, including date and time.
D
Shows status of the write protection alarm.
Note:
This alert is generated if the write lock parameter is cleared.
In addition, the active write protection alarm can be manually acknowledged in this
parameter group.
S
For hardware write protection: Shows status of the write protection
For software write protection:
LOCKED
NOT LOCKED
S
Determines the handling when a write protection alarm is generated (parameter
"WRITE_ALM").
0
The write protection alarm is not interpreted
1
The fieldbus host system is not alerted when a write protection alarm
is generated
2
Reserved for block alarms
3...7
The write protection alarm is issued with the corresponding priority
(3 = low priority, 7 = high priority) to notify the user.
8...15
The write protection alarm is issued with the corresponding priority
(8 = low priority, 15 = high priority) as a critical alarm.
0
D
Position of the write protection switch in the device
0 = Not write-protected
1 = Write-protected
Enable/clear write protection
Parameter description