Parameter description
Default:
SP
Index: 8
Access: r, w
in AUTO, MAN, O/S
Input:
SP_HI_LIM
Index: 21
Access: r, w
Input:
Default:
SP_LO_LIM
Index: 22
Access: r, w
Input:
Default:
SP_RATE_DN
Index: 19
Access: r, w
Default:
SP_RATE_UP
Index: 20
Access: r, w
Default:
ST_REV
Index: 1
Access: r
76
EB 8383-1 EN
Uninitialized
Note: This parameter is only active in the PID Block in the RCAS and ROUT modes. If it
is set to "Uninitialized", the PID Block cannot be placed into RCAS or ROUT modes.
N
Used to input the set point (reference variable) in AUTO mode.
Value and range of the PV_SCALE ±10 %
S
Used to input the upper range of the set point (reference variable).
Value and range of the PV_SCALE ±10 %
100
Note: If the lower range setting is changed in PV_SCALE, this value should be adapted
accordingly.
S
Used to input the lower range of the set point (reference variable).
Value and range of the PV_SCALE ±10 %
0
Note: If the lower range setting is changed in PV_SCALE, this value should be adapted
accordingly.
S
Used to input the ramp rate at which downward set point changes are acted on in the
operating mode AUTO.
38
3402823466 x 10
Note: If the ramp rate is set to "0", the set point will be used immediately. The rate limit
is active for control blocks in the AUTO mode only.
S
Used to input the ramp rate at which upward set point changes are acted on in AUTO
mode.
38
3402823466 x 10
Note: If the ramp rate is set to "0", the set point will be used immediately. The rate limit
is active for control blocks in the AUTO mode only.
S
Shows the revision level of the static data.
Note: The revision level will be incremented each time a static parameter is changed.