Upgrading The Pneumatic Positioner - Samson 4765 Mounting And Operating Instructions

Pneumatic positioner
Table of Contents

Advertisement

Upgrading the pneumatic positioner

8 Upgrading the pneumatic
positioner
The pneumatic positioner can be converted
into a Type 4763 Electropneumatic Position-
er with a conversion kit.
Note:
The version suitable for oxygen of the
Type 4765 Pneumatic Positioner can-
not be converted to form a
Type 4763 Electropneumatic Position-
er.
Besides the required Type 6109 or
Type 6112 i/p module (see Fig. 13), the as-
sociated conversion kit (including printed cir-
cuit boards, cable gland and mounting
screws) must be ordered.
Note:
For details on the converted
Type 4763 Positioner, refer to Mount-
ing and Operating Instructions
u EB 8359-2 EN.
With Type 6109:
1. Undo the connecting plate (6) and re-
move along with sealing element (7). Pull
off the hose (5).
2. Unscrew the connecting nipple (4) from
the housing.
3. Push the i/p module over the plug con-
nection onto the printed circuit board.
4. Insert the sealing element (7), on the bot-
tom, into the opening of the printed cir-
cuit board so that the restriction with fil-
ter (8) are situated on the right side
20
above the innermost of the two housing
holes (supply air) when the module
(dashed line in Fig. 13) is installed.
5. Secure the module and the printed circuit
board in the housing (two screws for the
module, one screw for the printed circuit
board). Subsequently assemble the cable
gland (1) along with the seal.
With Type 6112:
1. Proceed as described in steps 1 and 2 of
Type 6109
2. Place the i/p module on the plug of the
printed circuit board, and tighten the
side terminal screws.
3. Check whether the seals (10, 11) are
properly inserted on the bottom side.
When the module (dashed line in
Fig. 13) is installed, the seal with restric-
tion and filter must be situated on the
right side above the innermost of the two
housing holes (supply air).
4. Secure the module and the printed circuit
board in the housing (two screws for the
module, one screw for the printed circuit
board). Subsequently assemble the cable
gland (1) along with the seal.
Legend for Fig. 13
1
Cable gland
2
Printed circuit board
3
i/p converter module
4
Connecting nipple
5
Hose
6
Connecting plate
7
Sealing element
8
Restriction
10
Seal
11
Seal with restriction
EB 8359-1 EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents