Pneumatic Connection - Samson 3277-5 Mounting And Operating Instructions

Pneumatic actuator
Table of Contents

Advertisement

5.2.2

Pneumatic connection

The maximum permissible supply pressure is
specified in the order confirmation for the
control valve. It is, however, restricted to
6 bar in throttling service. See the 'Opera-
tion' section for restrictions in on/off service.
How and with which accessories the air sup-
ply is connected depends on the actuator
model and its direction of action. See 'Direc-
tion of action and signal pressure routing' in
the 'Design and principle of operation' sec-
tion.
Determine the lower and upper signal pres-
sure range values before connecting the sup-
ply air:
− The lower signal pressure range value
corresponds to the minimum value of the
bench range or operating range (when
the travel range is adapted, see 'Adapt-
ing the travel range' in the 'Start-up' sec-
tion).
− The upper signal pressure range value
corresponds to the maximum value of the
bench range or operating range (when
the travel range is adapted, see 'Adapt-
ing the travel range' in the 'Start-up' sec-
tion).
a) Type 3271-5
Version with fail-safe action "actuator stem
extends" (FA)
Î Connect the signal pressure to the bottom
signal pressure connection (S). See
Fig. 5-1.
EB 8310-1 EN
The signal pressure is routed to the bot-
tom diaphragm chamber and moves the
actuator stem (A7) upward opposing the
spring force.
Î Screw the vent plug into the connection
on the top diaphragm case.
Version with fail-safe action "actuator stem
retracts" (FE)
Î Connect the signal pressure to the top
signal pressure connection (S).
The signal pressure is routed to the top
diaphragm chamber and moves the ac-
tuator stem (A7) downward opposing the
spring force.
Î Screw the vent plug into the connection
on the bottom diaphragm case.
b) Type 3277-5
Operation with positioner (switchover plate)
Î Turn the switchover plate to align the
symbol (A2.4) matching the fail-safe
action and attachment side with the
marking (A2.5). See Fig. 5-5.
Operation without positioner (connecting
plate)
Î Turn the connecting plate to align the
symbol (A2.4) matching the fail-safe
action with the marking (A2.5). See
Fig. 5-5.
Î Make sure that the gasket for the con-
necting plate is correctly inserted.
Î The connecting plate has threaded holes
with NPT and G threads. Seal the con-
nection that is not used with the rubber
seal and square plug.
Installation
5-7