Static Pressure Effect; Power Supply Effect; Load Effect; Mounting Position Effect - Emerson Rosemount 3051N Reference Manual

Smart pressure transmitter for nuclear service
Hide thumbs Also See for Rosemount 3051N:
Table of Contents

Advertisement

Specifications and Reference Data
October 2016
A.2.5 Static pressure effect
Rosemount 3051ND
Zero Error (can be calibrated out at line pressure) Per 1000 psi
(6,9 MPa) line pressure
Range code Static pressure zero effect
(2)
0
± 0.125% URL for Ps
1
± 0.25% URL for Ps
± 0.05% URL for Ps
2, 3
± [0.1 + 0.1 (Ps-2000) / 1000]% URL for
Ps > 2000 psi (13,8 MPa)
± 0.1% URL for Ps
4, 5
± [0.2 + 0.2 (Ps-2000) / 1000]% URL
for Ps > 2000 psi (13,8 MPa)
1. Ps equals static line pressure applied.
2. Specification for Rosemount 3051N Range 0 is expressed in (% per
100 psi [689 KPa]).
Rosemount 3051ND
Span Error Per 1000 psi (6,9 MPa) line pressure
Range code Static pressure span effect
(1)
0
± 0.15% input reading
1
± 0.40% input reading
2, 3
± 0.10% input reading
± 0.20% input reading (uncertainty after
4, 5
calibration correction for systematic effects)
1. Specification for Rosemount 3051N Range 0 is expressed in [% per
100 psi (689 KPa)] up to 750 psi (5 171 KPa).
A.2.6 Power supply effect
Less than ±0.005% of calibrated span per volt for RDF  10
A.2.7 Load effect
No load effect other than change in voltage supplied to the
transmitter
A.2.8 Mounting position effect
Rosemount 3051ND/NG
Zero shifts up to ±1.25 in H
out; no span effect
Rosemount 3051NA
Zero shifts up to 2.5 in H
0 (63,5 mm), which can be calibrated
2
out; no span effect
Specifications and Reference Data
(1)
750 psi (5,2 MPa)
2000 psi (13,8 MPa)
2000 psi (13,8 MPa)
3626 psi (25 MPa)
2000 psi (13,8 MPa)
3626 psi (25 MPa)
0 (0,31 KPa), which can be calibrated
2
A.3 Functional specifications
A.3.1 Service
Liquid, gas, or vapor
A.3.2 Output
4–20 mA, user-selectable for linear or square root output; digital
®
signal based on HART
Protocol
A.3.3 Power supply
Load limitations
Maximum loop resistance is determined by the voltage level of the
external power supply, as described by:
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5) ohms
1935
1500
1000
500
0
10.5
20
30
Voltage (V dc)
Communication requires a minimum loop resistance of 250 ohms.
A.3.4 Temperature limits
Ambient
0 to 185 °F (-18 to 85 °C)
with meter option:
0 to 175 °F (-18 to 80 °C)
(1)(2)(3)
Process
0 to 250 °F (-18 to 121 °C) coplanar flange
0 to 300 °F (-18 to 149 °C) traditional flange
Storage
0 to 212 °F (-18 to 100 °C)
with meter option:
0 to 185 °F (-18 to 85 °C)
1.
Process temperatures above 185 °F (85 °C) require derating the ambient tem-
perature limits by 1.5 °F per degree above 185 °F.
2.
220 °F (104 °C) limit in vacuum service; 130 °F (54 °C) for pressures below 0.5
psia
3.
EPR O-ring is limited to 150 °F (66 °C) process temperature.
Reference Manual
00809-0100-4808, Rev DA
Design
Region
40
55
43