Siemens Simatic ET 200SP Manual page 31

Analog input module ai 2xu st
Hide thumbs Also See for Simatic ET 200SP:
Table of Contents

Advertisement

Error transmitting the data record
The module always checks all values of the transmitted data record. The module applies the
values from the data record only when all values have been transmitted without errors.
The WRREC instruction for writing data records returns the appropriate error codes if there
are errors in the STATUS parameter.
The following table shows the module-specific error codes and their meaning for parameter
data record 128.
Error code in the STATUS pa-
rameter
(hexadecimal)
Byte 0 Byte 1 Byte 2 Byte 3
DF
80
B0
DF
80
B1
DF
80
B2
DF
80
I0
DF
80
I1
Analog input module AI 2xU ST (6ES7134-6FB00-0BA1)
Manual, 12/2015, A5E36104728-AA
A.2 Parameter assignment and structure of the parameter data record
Meaning
xx
Number of the data record unknown
xx
Length of the data record incorrect
xx
Slot invalid or unavailable
xx
Incorrect version or error in the header
information
xx
Parameter error
Parameter data record
Solution
Enter valid number for data record.
Enter valid value for data record length.
Check the station to determine if the
module is plugged in or pulled.
Check assigned values for the parame-
ters of the WREC instruction.
Correct the version, length and number of
parameter blocks.
Check the parameters of the module.
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7134-6fb00-0ba1

Table of Contents