Parameter
Limit value for limit
1)
comparator
Switching differential
for limit comparator
1)
1)
Proportional band
Derivative time
Integral action time
Dead band (neutral
1)
zone)
36/57
The parameter is shown on the lower setpoint display (green) and the parameter value
on the upper / actual value display (red).
10
AL
7865p06/0200
Display
Value range
AL
-1999...+9999 digit
HYSt
0...999.9 digit
Pb.1
0.1...999.9 digit
dt
0...9999 s
rt
0...9999 s
db
0...999.9 digit
1)
Setting of the decimal place has an impact on this parameter.
CC1B7865en
7. Parameter settings
Factory
Remarks
setting
Output 4
0
HYSt
7865d10e/0300
ð
Chapter 8.2 «C112 – limit
comparator, controller type, setpoint
«SP1», locking»
1
Switching differential at the edges for
the limit comparators
ð
Chapter 8.2 «C112 – limit
comparator, controller type, setpoint
«SP1», locking»
10
Affects the P-response of the controller
80
Affects the D-response of the controller.
Within dt = 0, the controller has no D-
response.
For modulating controllers, dt = rt / 4 or
0 must be entered.
350
Affects the I-response of the controller.
With rt = 0, the controller has no I-
response
1
For floating output
Y
100%
-100%
7865d11/1099
05.12.2002
AL
Measured value
w
db
X
W
HVAC Products