Dell NX430 Owner's Manual page 27

Table of Contents

Advertisement

Particulate
Specifications
contamination
Conductive dust
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
Corrosive dust
Gaseous
Specifications
contamination
Copper coupon
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.
corrosion rate
Silver coupon
<200 Å/month as defined by AHSRAE TC9.9.
corrosion rate
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Related Links
Expanded operating temperature
NOTE: Applies to data center environments only. Air filtration requirements do
not apply to IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
NOTE: Applies to data center and non-data center environments.
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less than 60%
relative humidity.
NOTE: Applies to data center and non-data center environments.
27